The shock wave pulse generator model HVC-GS is specially designed for locating faults in power cables.

Technical Characteristics
Output voltages/dielectric testing voltages for each range | 0-4kVcc | 0-8kvcc | 0-16kVcc
Short-circuit current for each range |@ 4kVcc – 400mA
@ 8kVcc – 200mA
@ 16kVcc – 100mA
Maximum energy for each range |@ 8kVcc – 550J
@ 16kVcc – 550J
@ 32kVcc – 550J
Grounding |Automatic
Coupler|ICE (Impulse Current Method)
Dimensions (height, width, depth) |Equipment: 310, 483, 520 mm
Rack (19’’): 360 x 540 x 540 mm
Weight |Equipment: 55 kg
Rack (19’’): 15 kg
Power supply|220 Vca/50Hz
Operating temperature |-10 °C … +50 °C
Price on request
Rent Banner The product is available for rent

Description

The output voltage can be continuously adjusted within the ranges of 0-4 kV, 0-8 kV, and 0-16 kV.

A peak energy of 550 J at each range provides an excellent balance of power, weight, and size necessary for precisely pinpointing cable faults using the acoustic method in conjunction with the RPF A/I fault pinpointing device.

The powerful high-voltage source allows for dielectric testing at any of its ranges, up to 16 kV. It features a damped grounding system that automatically discharges the internal capacitors and the tested installation after the test is completed.
The grounding, power supply, and high-voltage terminals are located on the rear of the unit and are easily accessible for the operator.

Highlights

  • Compact, portable, and robust.
  • Continuously adjustable voltage.
  • Automatic grounding.
  • Discharge energy optimized by capacitor switch.
  • High energy peak for precise and effective localization.

Scope of supply:

  • 220V AC power cable — 5 mts.
  • Shielded high-voltage output cable — 5 mts.
  • Safety grounding connection cable — 5 meters.
  • Direct discharge rod.
  • Operation manual.