Compact system for testing and fault locating on low and medium voltage cables.

 

Highlights

  • Compact and robust.
  • Modular and configurable.
  • 4 high voltage output ranges.
  • Suitable for mounting in medium-small utility vehicles.
  • Safe and rapid fault location.
  • Includes various fault pre-location methods (TDR, IF-TDR,ICE,ARM,M-ARM).
  • High energy peak for precise and effective pinpointing
Price on request
Rent Banner The product is available for rent

The HVC-FL1 is a compact system for testing and fault location in low and medium voltage cables. The TS80R reflectometer features the most advanced pre-location methods, including TDR and IF-TDR (Time Domain Reflection and Intermittent TDR), ICE (Impulse Current), ARM and M-ARM (Arc Reflection Method and Multiple ARM), and DECAY (Voltage Decay).

With its energy peak of 2048J across four ranges—4, 8, 16, and 32 kV (1024J — 3072J optional)—it provides the necessary power to accurately detect cable faults using the acoustic method with the RPF A/I fault pinpointing device. The powerful high-voltage source allows testing at any voltage level between 0 and 32 kV.

Typical Configuration:

  • Control module
  • Reflectometer TS 80R
  • Tone generator RGT 100R
  • Range switching switch (4, 8, 16, or 32 kV)
  • Function switching switch
    (Filter, Direct, and Signal)

 

Cable reels with 50 meters or a side reel with 20 meters can be chosen:

  • Output cable for high voltage (AT);
  • Safety ground cable
  • Operational ground cable
  • Power supply cable

Techical Specification

TS 80R
Distance Range|128m to 250 Km @ 80m / μseg
Pulse Width|100ns to 6μs
Pulse Amplitude|20Vp a 100Vp
Resolution|1 mts@vp2=80mts/μseg
Sampling Frequency|80 Mhz
Methods|TDR, IF-TDR, ICE, ARM, M-ARM and DECAY
Measurement|Movable On-Screen Cursors
VP/2|Adjustable between 50m/μs and 150m/μs
Zoom|Yes
Memory|>1000 reflectograms
Connections|USB2.0 – BNC
Display|10.4” TFT High-Contrast Color Display, 800 x 600 Pixels, LED Backlight
RGT 100R
Selectable Frequencies|10 kHz – 1,48 – 480 Hz
Output Power|Adjustable from 0 to 100 VA
Frequency Range|0,48 – 1,48 – 10Hz
Output Impedance Ω|1 – 2 – 5; 10 – 30 – 100; 300 – 100
Output Mode |Rectangular; Continuous
Measurement|LCD graphical display
HVC-FL1
High-Voltage Testing (kVcc)|0 – 4, 0 – 8, 0 – 16 y 0 – 32
Short-Circuit Current per Range|@ 4kVcc – 640mA @ 8kVcc – 320mA @ 16kVcc – 180mA @ 32kVcc – 90mA
Maximum Energy per Range|@ 4kVcc – 2048 J @ 8kVcc – 2048 J @ 16kVcc – 2048 J @ 32kVcc – 2048 J
Discharge Frequency|4 – 6 seg. Manual
Function Switch|Yes / Manual (ARC filter, power, and signal)
Range Switch|Yes/M (4,8,16,32kV)
Grounding|Automatic
Filters / Couplers|ARM – ICE
Phase Switch|Manual (R, S, T, and Earth)
High-Voltage Cable|3 x 50 meters, shielded, 6 mm2
Power Cable|50 mts. 3 x 2,5 mm2
Ground / Return|50 meters 10 mm2 / 50 meters 10 mm2 armored
Dimensions mm (Height, Width, Depth)|Control module - 1355 x 635 x 735; Cable reels- 1900 x 830 x 600
Total Weight (Approximate) |235 kg
Power Supply|220 Vca/50Hz (110 Vca/60hz optional)